Digital interfaces (external interfaces)
FAM 5
en-US
Page 80 / 148
BEWA FAM5 4166129a en-us 2019-03-04.docx
2019-03-04
Outlets (isolated contacts):
During the follow-up phase (cooling and emptying phase) of the unit, the
outlet "Operating state" continues to remain closed and opens only after
completing the follow-up phase and shutdown of the pumps.
•
Duration of the cooling phase: 60 seconds (only for integrated and
activated heater)
•
Duration of the emptying phase: max. 45 seconds
+ 24 V DC, max. 1 A,
DC-12
+ 24 V DC, max. 1 A,
DC-12
+ 24 V DC, max. 1 A,
DC-12
Outlet, for example to PLC
Outlet, for example to PLC
Outlet, for example to PLC
Operating status
Filter clogged
Device ready
FAM terminal strip
FAM scope of delivery
NO, closes if the unit is in
operation
NO, closes if the filter is
not contaminated
NO, closes if the main
switch is ON and there is
not fault. Unit is ready for
operation