captures the current signal waveform reflected back and forth in the cable when
impact.
C. Location: Cable fault pinpoint use.
D. DC output: It can output DC high-voltage to test cable.
5. Confirm that regulator knob is at zero and stop key is in non-locked state. Press the
start key to start the instrument, and you can hear "plump" sound inside the
instrument, which means that the high-voltage output of the instrument is connected.
6. Press the ignition button (except DC output mode), and the instrument will perform
arcing ball-gap pulling in according to the set time. You can hear the ball-gap
regularly pulling in sound.
7. Adjust regulator knob up to the required voltage (The boost can be slightly low, and
gradually increased, but do not set voltage exceeding the voltage gear when it’s the
first connection).
8. The operator pulse reflect meter (TDR) will test input signals and read fault
distance if it’s cable fault location mode.
9. When the test is completed, the regulator knob should be back to zero, and press
stop key to stop and it will automatically discharge. If an emergency situation
happened, you can press stop key to stop directly and it’ll automatically discharge.
10. If you need to adjust high-voltage test, repeat steps 4-9. If you want to stop the test,
turn off the power switch.
11. Artificial discharge, confirms discharged completely, and then remove all the
wiring.
IV. Warning and Note
1. Do not set voltage over the voltage gear when boosting.
2. Do not strongly pull and fold the output high-voltage silicone cable, power line,