UPS5000-S-1200 kVA
User Manual
4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
118
Item
Description
Default Value Value Range
(C10)
Cell float
voltage (V/cell)
Specifies the battery float
charging voltage.
2.25 V/cell
2.23 V/cell to
2.30 V/cell
Cell equalized
volt. (V/cell)
Specifies the battery equalized
charging voltage.
2.35 V/cell
2.30 V/cell to
2.40 V/cell
Dis. cur. 0.1C
EOD (V/cell)
Specifies the EOD threshold
when the discharging current is
0.1C, 0.3C, 0.5C, and 1.0C
respectively.
1.80 V/cell
1.8–1.9
Dis. cur. 0.3C
EOD (V/cell)
1.80 V/cell
1.8–1.9
Dis. cur. 0.5C
EOD (V/cell)
1.75 V/cell
1.75–1.85
Dis. cur. 1.0C
EOD (V/cell)
1.60 V/cell
1.6–1.75
Sched. shallow
dis. test
When certain conditions are met,
the charger shuts down, and
batteries supply power to loads.
The system records the battery
discharge data as the reference
for battery capacity and lifespan.
Disable
Disable, Enable
Shallow dis.
test dis. ratio
(%)
Set the proportion of the
discharge capacity to the total
discharge capacity. The value is
configurable in any mode.
20%
10%–50%
iBOX Settings
Figure 4-31
iBOX settings