UPS5000-S-1200 kVA
User Manual
10 Alarm List
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
196
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Cause
Solution
incorrect.
2.
Check that the neutral wire to the power
distribution system is normal.
0006-1
Mains
undervoltage
Minor
The mains is
not normal.
The power
module
sampling
circuit is not
normal.
Check whether the mains voltage ranges
from 80 V (excluding 80 V) to 176 V. If no,
the mains monitoring circuit for the power
module is faulty. Replace the faulty
module.
0010-1
Abnormal
bypass voltage
Minor
The bypass
voltage range
is not
correctly set.
The bypass
input voltage
is not normal.
1.
Check the bypass input voltage or cable
connections with a multimeter.
2.
Check the voltage system and bypass
voltage thresholds configured on the
LCD.
0010-2
The bypass
frequency
range is not
correctly set.
The bypass
input
frequency is
not normal.
1.
Check the bypass input voltage or cable
connections with a multimeter.
2.
Check the bypass input frequency.
Check the rated frequency and
frequency range configured on the LCD.
0011-1
Bypass phase
reversed
Minor
The phase
sequence of the
three-phase
bypass input is
reversed.
Check whether the cable phase sequence is
correct using a multimeter. If no multimeter
is available, exchange the positions of any
two cables.
0012-1
Bypass neutral
absent
Minor
The neutral wire
of bypass input
is not installed
properly.
1.
Secure or connect the neutral wire to the
cabinet if it is loose or disconnected.
2.
Check that the neutral wire to the power
distribution system is normal.
0020-1
Battery
connected
reversely
Critical
Batteries are not
properly
installed.
1.
Check whether battery polarities are
correctly installed by using a
multimeter. If no, correct the
installation.
2.
Check whether the battery input voltage
of the UPS is normal. If yes, the battery
sampling circuit of the power module is
faulty. Replace the power module.
0021-1
Battery EOD
Critical
The battery
voltage reaches
the EOD voltage
If the BCB box is configured, check
whether the BCB box trips. If it trips, close
the BCB box switch.