5 Operations
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
175
Figure 5-15
Log
Step 2
Choose logs that have been queried from the
Log
drop-down list box, and click
Export
.
----End
5.7 Transferring to Maintenance Bypass Mode
Prerequisites
The maintenance bypass unit has been installed.
Context
Strictly observe the following procedure to transfer the UPS to maintenance bypass mode.
Otherwise, loads may power off.
In maintenance bypass mode, the mains supplies power to the loads directly over the
maintenance bypass. If the mains is abnormal, the loads may power off.
Procedure
Step 1
Manually switch the UPS to bypass mode.
Step 2
Turn on the maintenance bypass switch.
After the UPS transfers to maintenance bypass mode, the
Maint. breaker closed
and
Bypass mode
alarms are displayed on the MDU.
----End