UPS5000-S-1200 kVA
User Manual
4 User Interface
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
112
Item
Description
Default Value Value Range
overdischarge.
Intra-rack power
module start delay (s)
can be set
to a value ranging from 0.5 to
120.
Inter-rack power module
start delay (s)
can be set to a
value ranging from 2 to 120. The
preset value of
Inter-rack power
module start delay (s)
is 5.0.
The start delay of a module in a
rack varies depending on the rack
number and module number. #1
module in rack 1 does not have a
start delay.
Maintenance
bypass cabinet
If the maintenance bypass unit is
configured, set this parameter to
Enable
.
Disable
Disable, Enable
Intelligent
detection
module
N/A
Disable
Disable, Enable
Input Settings
Figure 4-25
Input settings
Item
Description
Default Value Value Range
D.G. mode
Set this parameter to
Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
Disable
Disable, Enable
D.G. power
limiting (kVA)
Set these two parameters to
control the valid input current
800 kVA
0 kVA to 5000
kVA