UPS5000-S-1200 kVA
User Manual
8 Technical Specifications
Issue 04 (2019-06-25)
Copyright © Huawei Technologies Co., Ltd.
193
Item
Specifications
The UPS runs continuously at 125% load at 40°C;
generates only alarms and uses overtemperature protection
at 125–150% load.
The UPS runs for 5 minutes at bypass single-phase or
three-phase load 150%–200% at 40°C; runs for 1 minute at
bypass single-phase or three-phase load greater than 200%
at 40°C.
The UPS runs for 100 ms when the load is greater than
1000%.
Table 8-8
System electrical specifications
Item
Specifications
Parallel reliability of
power units
Redundant parallel signals
Parallel ECO function of
power units
Supported
Number of parallel UPSs
2