TP48200A-HX09A1 and TBC300A-DCA5 Telecom
Power
User Manual
A Technical Specifications
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
82
Item
Specifications
interference (EMI)
Radiated emission (RE)
Class A, EN300386
Harmonic
IEC 61000-3-12
Fluctuation and flick
IEC 61000-3-11
Electromagnetic
susceptibility (EMS)
Electrostatic discharge (ESD)
Contact discharge: 6 kV (criterion B); air discharge:
8 kV (criterion B)
Electrical fast transient (EFT)
EN61000-4-4
Signal port: ±1 kV (criterion B); AC power port: ±2
kV (criterion B); DC power port: 2 kV (criterion B)
Radiated susceptibility (RS)
Field strength: 10 V/m (criterion A)
Conducted susceptibility (CS)
Signal port: 3 V (criterion A); power port: 10 V
(criterion A)
Surge susceptibility
EN61000-4-5
AC and DC power ports: differential mode: ±2 kV
(criterion B); common mode: ±4 kV (criterion B).
Signal port: differential mode: 0.5 kV (criterion B);
common mode: 1 kV (criterion B)
A.4 Cabinet Specifications
Table A-4
Cabinet specifications
Function
Specifications
Dimensions (H x W x D)
900 mm x 650 mm x 650 mm (excluding the base and protruding part)
Base (H x W x D)
100 mm x 650 mm x 650 mm
Cabinet weight
TP48200A-HX09A1: ≤ 75 kg (without rectifiers)
TBC300A-DCA5: ≤ 50 kg (without batteries)
Protection level
TP48200A-HX09A1: IP55
TBC300A-DCA5: IP34
Installation mode
TP48200A-HX09A1: installed on a floor, installed against a wall,
combined with a battery cabinet, or stacked on a battery cabinet
TBC300A-DCA5: installed on a floor, installed against a wall (with a
clearance of greater than 100 mm), combined with a power cabinet or
battery cabinet, stacked under a power cabinet, or stacked on or under a
battery cabinet
Maintenance mode
Operated and maintained from the front
Cable routing
Routed in and out from the bottom