4 Maintenance
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
71
Step 6
Place the alarm cables in sequence and secure the screws.
Step 7
Reinstall the shell of the door status sensor.
----End
Follow-up Procedure
Check that the door status alarm is cleared.
4.4.12 Replacing a Temperature and Humidity Sensor
Prerequisites
An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools
are available.
The new temperature and humidity sensor is intact.
Procedure
Step 1
Connect the ground cable of the ESD wrist strap, and wear the ESD wrist strap and ESD
gloves.
Step 2
Remove the temperature and humidity sensor cable from the user interface module (UIM), as
shown in Figure 4-22.
Figure 4-22
Removing the temperature and humidity sensor cable
Step 3
Remove the temperature and humidity sensor, as shown in Figure 4-23.
1.
Hold down the button on the sensor and remove the upper cover.
2.
Record the positions where cables connect to the base and remove the cables.
3.
Unscrew the sensor base.