TP48200A-HX09A1 and TBC300A-DCA5 Telecom
Power
User Manual
3 Components
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
23
Figure 3-3
AC input unit
(1) AC input circuit
breaker
(2) AC input terminal (neutral
wire)
(3) AC surge protective device
(SPD)
Figure 3-4
AC output unit (German-standard socket and RCD)
(1) German-standard
socket
(2)
RCD
(3) AC load circuit breaker and neutral wire
terminal
Table 3-1 describes the AC PDU configurations for the TP48200A-HX09A1.
Table 3-1
AC PDU configurations
Power Grid Mode
AC Input
Circuit
Breaker
AC Surge Protection
Class
AC Load
Circuit
Breaker
Maintenance
Socket and Its
Protection Mode
Optional: 220 V AC
single-phase
One 3-pole 63
A circuit
breaker
Class B. The normal
current (In) is 30 kA,
and the maximum
current (Imax) is 60 kA.
Two 1-pole
10 A circuit
breakers
German-standard
socket and 10 A
residual current
device (RCD)
Optional: 220/380 V AC
three-phase, four-wire