SUN2000-(33KTL-A, 36KTL, 42KTL)
User Manual
5 Connecting Cables
Issue 07 (2018-05-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
43
Figure 5-5
Connecting a ground cable
To enhance the corrosion resistance of the ground terminal, apply silica gel or paint on the ground
terminal after connecting the ground cable.
----End
5.3 Connecting AC Output Power Cables
Prerequisites
A three-phase AC switch needs to be configured outside the AC side of the SUN2000. To
ensure that the SUN2000 can safely disconnect from the power grid under abnormal
conditions, select an appropriate overcurrent protection device according to local power
distribution regulations.
Do not connect loads between the SUN2000 and the AC switch.
Context
If you connect a ground cable to the ground point on the chassis shell in a scenario with
no neutral wire, you are advised to use a three-core (L1, L2, and L3) outdoor cable as the
AC output power cable for the SUN2000-33KTL-A/36KTL.
If you connect a ground cable to the ground point in the maintenance compartment in a
scenario with no neutral wire, you are advised to use a four-core (L1, L2, L3, and PE)
outdoor cable as the AC output power cable for the SUN2000-33KTL-A/36KTL.
If you connect a ground cable to the ground point on the chassis shell in a scenario with a
neutral wire, you are advised to use a four-core (L1, L2, L3, and N) outdoor cable as the
AC output power cable for the SUN2000-33KTL-A/36KTL.