NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
2 Product Overview
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
24
Item
Specifications
Storage humidity
5%–95% RH (non-condensing)
Altitude
0–4000 m (derated when the altitude is in
the range of 1000–4000 m)
Temperature adjustment range
15–45°C
Temperature adjustment precision
1°C; temperature change rate < 5°C/h
Humidity adjustment range
20%–80% RH
Humidity adjustment precision
5% RH
Air outlet static pressure
0–450 Pa
2.6 Technical Specifications
It is recommended that 4x6 mm
2
cables be used for the active power supply to
NetCol8000-C220 and NetCol8000-C260 when they are equipped with heating and
humidification functions. If 4x10 mm
2
cables are to be used, change the screws on the power
cable clip. Find the corresponding screws in the accessory.
Table 2-6
Parameter table
Model Config
uration
Power
system
Maximum
Current (with
Heating and
Humidificatio
n/Without
Heating or
Humidificatio
n)
Recommended
Switch (with
Heating and
Humidification/
Without Heating
or
Humidification)
Cable Diameter
(with Heating and
Humidification/
Without Heating
or
Humidification)
Dimension
s (H x W x
D, mm)
NetCol
8000-C
070
Single
route
380–48
0V AC,
3PH,
50/60H
z
15.2A/4.7A
C25/C16
4 x 4mm
2
/4 x
2.5mm
2
2000 x 900 x
1000
(single-door)
Dual
route
380–41
5V AC,
3PH,
50/60H
z
Active:
15.2A/4.7A
Standby: 4.7A
Active: C25/C16
Standby: C16
Active: 4 x 4mm
2
/4
x 2.5mm
2
Standby: 4 x
2.5mm
2
NetCol
Single
380–48
30.4A/9.4A
C40/C25
4 x 6mm
2
/4 x 4mm
2
2000 x 1800