NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
170
Item
Method
Troubleshooting
Water leakage
sensor
Check that the water leakage
sensor is securely installed.
Retighten the cables.
Chilled water
pipe
Check that the thermal
insulation foam on the chilled
water pipe is intact.
Rewrap the thermal insulation foam.
Check that the pipe support is
intact and securely installed.
Secure the base.
Check that pipes do not leak.
Close the water inlet stop valve and
repair leaks.
Check that the smart cooling
product drainpipe is free from
leaks and blockages.
If the drainpipe leaks, repair the leaks. If
the drainpipe is blocked, clear the
blockage inside the pipe.
Water leakage
sensor
Check that the water leakage
sensor is securely installed.
N/A
Differential
pressure
sensor
Check that the pressure inlet
tube is not blocked or
over-bent.
Reinstall the pressure inlet tube.
Check that cables to the
differential pressure sensor
are securely connected.
Reconnect the cables.
Motorized
Damper/Gravi
ty Damper
(Applicable to motorized
damper) Check that cables to
the actuator are securely
connected.
Reconnect the cables.
Check that the damper is
securely fixed.
Fix the damper again.
Direct
free-cooling
plenum
Check that cables to the
actuator are securely
connected.
Reconnect the cables.
Check that the damper is
securely fixed.
Fix the damper again.
Check that the pressure inlet
tube is not blocked or
over-bent.
Reinstall the pressure inlet tube.
Check that cables to the
differential pressure switch
are securely connected.
Reconnect the cables.
Cap
Check that the cap is reliably
secured.
Tighten the cap again.
Check that the air deflector is
adjusted to a proper angle.
Adjust the angle of the air deflector
again.