NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
182
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
NOTE
After the fault is rectified,
click
Clear
on the alarm
page to manually clear the
alarm.
a104
In-cabinet
water
overflow
Critical N/A
1.
There is water at the
detection position of the
water overflow sensor.
2.
The cables to the water
overflow sensor are loose or
damaged.
3.
The water overflow sensor
is faulty.
1.
Check and clear the
water.
2.
Check the cables to
the water overflow
sensor.
3.
Maintain or replace
the water overflow
sensor.
a105
Indoor fan
failure
Critical An alarm is
triggered.
The indoor fan is faulty.
Maintain or replace the
indoor fan.
a108
Cold aisle
temperature
invalid
Major
An alarm is
triggered.
1.
The cables to the
temperature sensor are
loose or damaged.
2.
The temperature sensor is
faulty.
1.
Check the cables to
the temperature
sensor.
2.
Maintain or replace
the temperature
sensor.
a109
Cold-aisle
humid
invalid
Major
An alarm is
triggered.
1.
The cables to the
temperature and humidity
sensor are loose or
damaged.
2.
The temperature and
humidity sensor is faulty.
1.
Check the cables to
the temperature
sensor.
2.
Maintain or replace
the temperature and
humidity sensor.
a110
Cold aisle
temp/humid
board comm
failed
Major
An alarm is
triggered.
1.
The cables to the T/H
sensor are loose or
damaged.
2.
The DIP switch of the T/H
sensor is set incorrectly.
3.
The T/H sensor is faulty.
4.
The communication port of
the control board is faulty.
1.
Check the cables to
the T/H sensor.
2.
Set the DIP switch of
the T/H sensor
correctly.
3.
Maintain or replace
the T/H sensor.
4.
Maintain or replace
the control board.
a111
Hot aisle
temperature
invalid
Major
An alarm is
triggered.
1.
The cables to the
temperature sensor are
loose or damaged.
2.
The temperature sensor is
faulty.
1.
Check the cables to
the temperature
sensor.
2.
Maintain or replace
the temperature
sensor.
a112
Cold aisle
humidity
invalid
Major
An alarm is
triggered.
1.
The cables to the
temperature and humidity
sensor are loose or
damaged.
2.
The temperature and
1.
Check the cables to
the temperature
sensor.
2.
Maintain or replace
the temperature and