NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
217
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
inlet
solenoid
valve are
loose or
damaged.
into the
humidifier
pan from the
water inlet
pipe of the
humidifier.
5.
Verify that
cables to the
water inlet
solenoid
valve are
properly
connected.
A193-01
Air-side diff
pressure sensor
fault
Major
An alarm is
triggered.
1.
The
differential
pressure
sensor cable
is loose or
damaged.
2.
The pressure
tube of the
differential
pressure
sensor is
reversely
connected.
3.
The
differential
pressure
sensor is
faulty.
1.
Check the
cable
connection
to the
differential
pressure
sensor.
2.
Check the
tube
connection
to the
differential
pressure
sensor.
3.
Maintain or
replace the
differential
pressure
sensor.
A208-01
Indoor fan 1
blocked alarm
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The indoor
fan blade is
stuck.
2.
The indoor
fan is faulty.
1.
Clear the
blockage.
2.
Maintain or
replace the
indoor fan.
Indoor fan 2
blocked alarm
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The indoor
fan blade is
stuck.
2.
The indoor
fan is faulty.
1.
Clear the
blockage.
2.
Maintain or
replace the
indoor fan.
Indoor fan 3
blocked alarm
Major
An alarm is
triggered, and
the
corresponding
fan is shut
1.
The indoor
fan blade is
stuck.
2.
The indoor
fan is faulty.
1.
Clear the
blockage.
2.
Maintain or
replace the
indoor fan.