212
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
alarm
threshold is
inappropriat
e.
4.
The value
detected by
the
temperature
and
humidity
sensor is
different
from the
actual value.
4.
Calibrate or
replace the
temperature
and
humidity
sensors.
A097-01
Supply-water
high
temperature
alarm
Major
An alarm is
triggered.
1.
The
temperature
of chilled
water is
higher than
the supply
water high
temperature
alarm
threshold.
2.
The supply
water high
temperature
alarm
threshold is
inappropriat
e.
3.
The supply
and return
water pipes
are reversely
installed.
4.
The supply
and return
water
sensors are
reversely
installed.
5.
The supply
water
temperature
displayed is
different
from the
actual
temperature.
1.
Check the
temperature
of supplied
chilled
water.
2.
Adjust the
supply water
high
temperature
alarm
threshold.
3.
Exchange
the positions
of the supply
and return
water pipes.
4.
Exchange
the positions
of the supply
and return
water
sensors.
5.
Calibrate or
replace the
supply water
temperature
sensor.