Symptom
Possible Cause
Reference Solution
The humidifier water
pump fails to supply
water.
The water pump is faulty or the
cable connection is incorrect.
Replace the water pump or reconnect the
cable.
The water pump is blocked.
Replace the water pump.
The water pump is sealed by gas.
Restart the water pump
The humidification
capacity is insufficient.
The wet film humidifier wears out
and deteriorates.
Replace the wet film humidifier.
The air filter is blocked.
The air filter has been used for too
long and become dusty.
Replace the air filter.
The differential pressure switch is
faulty.
Replace the differential pressure switch.
The pressure difference
cannot be controlled.
The differential pressure sensor is
faulty.
Replace the differential pressure sensor.
The pressure tube is blocked or
over-bent.
Replace the pressure tube or route the
pressure tube again.
The motorized damper
does not operate.
The actuator cable is not properly
connected.
Check and reconnect the cable to the
motorized damper actuator.
The actuator is faulty and does not
operate.
Replace the actuator.
The motorized damper is stuck.
Replace the motorized damper.
The direct free-cooling
plenum does not operate.
The actuator cable is not properly
connected.
Check and reconnect the cable to the direct
free-cooling plenum actuator.
The actuator is faulty and does not
operate.
Replace the actuator.
The direct free-cooling plenum is
stuck.
Replace the direct free-cooling plenum.
The air filter of the fresh
air unit is blocked.
The air filter has been used for too
long and become dusty.
Clean or replace the air filter.
The differential pressure switch is
faulty.
Replace the differential pressure switch.
6.7 Parts Replacement
6.7.1 Replacing the Air Filter
Context
Tool: Phillips screwdriver