32
(Optional) Teamwork Settings
10.3
No.
Item
Teamwor
k group
no.
Air
condition
er
address
Enable
teamwor
k CAN
resistor
Teamwo
rk
function
Networking
mode
Number of
air
conditioners
in this group
Number of
running air
conditioners
in this group
Rotation
function
1
1
1
Yes
Enable
CAN
network
8
6 (2 standby)
Enable
2
1
2
No
Enable
CAN
network
/
/
/
3
1
3
No
Enable
CAN
network
/
/
/
...
...
...
...
...
CAN
network
...
...
...
7
1
7
No
Enable
CAN
network
/
/
/
8
1
8
Yes
Enable
CAN
network
/
/
/
The table uses 8 smart cooling products in CAN teamwork as an example.
1. Teamwork group no.: A maximum of four groups, with the same teamwork control number, can be
assigned (1
–4) for one teamwork networking.
2. Smart cooling product address: In a teamwork control group, each smart cooling product address
(1-32) must be unique, and the smart cooling product with minimum address is the master smart
cooling product.
3. Networking mode: The networking mode set on the screen must be consistent with the actual
networking mode.
4. Enable teamwork CAN resistor: Set the parameter if CAN teamwork is used. Set the parameter to
ON for the first and eight smart cooling products.
5. Number of smart cooling products in this group: Indicates the number of precision smart cooling
products in a group. The value is an integer ranging from 1 to 32.
6. Number of running smart cooling products in this group: Specifies the number of running
NetCol8000-As in a group. The value ranges from 1 to the number of NetCol8000-As in the group.
7. Rotation function: Enable the active and standby smart cooling products to work alternately. This
function is recommended when the heat load is even.