34
Choose
Maint
>
Wizard Startup
to enter
wizard startup.
Open the
Service Expert
app.
Tap
StartUp
>
Offline Activation
on
APP
After tapping
Yes
, the barcode and the
verification code are shown on the screen.
Start
Tap
Start
on the home screen.
Enter
Bar code
and
Verification code,
and tap
Generate PWD.
Enter the generated startup password on
the screen of smart cooling product
.
Tap
Yes
on
Wizard Startup
screen to enter
wizard startup.
Go to step 2
Refrigerant is fully charged?
No
Tap
No
on
Wizard Startup
screen to exit
wizard startup.
Yes
Charge the remaining amount of refrigerant
from low-pressure needle valve.
1. First startup flowchart
Tap Enter. The screen turns to
Wizard
Startup.
Tap
Start
on the home screen and choose
Maint > Diagnostic Mode > Enter.
Set the compressor to 3000 rpm
.
Choose
Maint
>
Diagnostic Mode > Exit
and tap
Shutdown
on the home
screen.
If there is no water supply,
clear the humidifier
commissioning item when
wizard startup
commissioning. After
Wizard startup
, lift the low
liquid level detector. After at
least 5 seconds, choose
Running
>
Device Details
>
Humidifier
to check that
Low liquid level states
is
Triggered.
Choose
Running
>
Device Details
>
Humidifier
>
Advanced
to check that
Humidifier
pump control states
is
On,
the humidifier is functional.
Success
2. Wizard startup flowchart
Success
Success
Success
Success
Outdoor fan commissioning
Electric heater
commissioning
Cooling system
commissioning
Humidifier commissioning
Indoor fan commissioning
Commissioning
interrupted
(Handle the
fault by
referring to the
tips displayed
on the home
screen.
Perform wizard
startup after
the handling.)
Start
End
Precautions
Yes
No
No
Fail
Fail
Fail
Fail
Yes
Fail
Select commissioning items