Mapping Between Saturation Temperatures and Pressure of R410A
Saturation
temperature (ºC)
Gauge
(MPa)
Saturation
temperature (ºC)
Gauge
(MPa)
Saturation
temperature (ºC)
Gauge (MPa)
10
0.99
19
1.31
28
1.69
11
1.02
20
1.35
29
1.74
12
1.05
21
1.39
30
1.79
13
1.09
22
1.43
31
1.84
14
1.12
23
1.47
32
1.89
15
1.16
24
1.51
33
1.94
16
1.19
25
1.56
34
1.99
17
1.23
26
1.60
35
2.05
18
1.27
27
1.65
36
2.10
4
7/8 inch Gas pipe
inverted trap
3/4 inch Liquid
pipe inverted trap
5/8 inch Liquid
pipe inverted trap
1 inch Gas pipe
inverted trap
3
Installing the Indoor Unit
Oil Trap and Inverted Trap (Unit: mm)
2.2
7/8 inch Oil trap
1 inch Oil trap
1. Read the related user manual or instructions before installing the NetCol8000-A.
2. The unit in this document is a fully configured NetCol8000-A. If some components are not
configured, skip the corresponding steps.
3. You are recommended to use tools that are fully insulated when installing devices.
4. Only engineers from the manufacturer or engineers certified by the agent are allowed to
install, commission, and maintain smart cooling product. Otherwise, personal injuries and
device damage may be caused, which is beyond the smart cooling product warranty range.