26
Indoor Unit
Outdoor Unit
Refrigerant Charge Amount (L) (L is total one-
way pipe length)
0m
<
L ≤
10m
10m
<
L ≤ 60m
60m
<
L ≤ 100m
NetCol8000-A045D
NetCol500-A060/
NetCol500-A120 system1/
NetCol500-A120 system2
9.4
9.4+ (L-10)
×0.21
9.4+ (L-10)
×0.28
NetCol500-A080
13.4
13.4+ (L-10)
×0.21 13.4+ (L-10) ×0.28
NetCol8000-A045D
including a low-
temperature
component
NetCol500-A060/
NetCol500-A120 system1/
NetCol500-A120 system2
32.9
32.9+ (L-10)
×0.21 32.9+ (L-10) ×0.28
NetCol8000-A045U
NetCol500-A060/
NetCol500-A120 system1/
NetCol500-A120 system2
8.8
8.8+ (L-10)
×0.21
8.8+ (L-10)
×0.28
NetCol500-A080
12.8
12.8+ (L-10)
×0.21 12.8+ (L-10) ×0.28
NetCol8000-A045U
including a low-
temperature
component
NetCol500-A060/
NetCol500-A120 system1/
NetCol500-A120 system2
32.3
32.3+ (L-10)
×0.21 32.3+ (L-10) ×0.28
NetCol8000-A090D
system1
NetCol500-A060/
NetCol500-A120 system1
9.4
9.4+ (L-10)
×0.21
9.4+ (L-10)
×0.28
NetCol500-A080
13.4
13.4+ (L-10)
×0.21 13.4+ (L-10) ×0.28
NetCol8000-A090D
system2
NetCol500-A060/
NetCol500-A120 system2
9.4
9.4+ (L-10)
×0.21
9.4+ (L-10)
×0.28
NetCol500-A080
13.4
13.4+ (L-10)
×0.21 13.4+ (L-10) ×0.28
NetCol8000-A090D
system1 including a
low-temperature
component
NetCol500-A060/
NetCol500-A120 system1
32.9
32.9+ (L-10)
×0.21 32.9+ (L-10) ×0.28
NetCol8000-A090D
system2 including a
low-temperature
component
NetCol500-A060/
NetCol500-A120 system2
32.9
32.9+ (L-10)
×0.21 32.9+ (L-10) ×0.28
NetCol8000-A060D
NetCol500-A080
15.5
15.5+ (L-10)
×0.23 15.5+ (L-10) ×0.31
NetCol500-A110
22
22+ (L-10)
×0.23
22+ (L-10)
×0.31
If the R410A refrigerant is provided by Huawei, put the refrigerant steel vessel upside down when
charging in the refrigerant. If the refrigerant is not provided by Huawei, check with the refrigerant
provider whether the steel vessel has a siphon. If the vessel has a siphon, put it upside up when
charging in refrigerant. If the vessel has no siphon, put it upside down when charging in refrigerant.
These measures ensure that the refrigerant is charged in the liquid form.
If one NetCol8000-A090D is used with two NetCol500-A060s (or one NetCol500-A120) and the L
is 80 m, the 9.4 + (80-10)
×
0.28=29 kg needs to be filled in each compressor system. In total, the
NetCol8000-A090D needs to charge 58 kg R410A.