No.
Parameter
Description
Remarks
5
Active power
change gradient
(%/s)
Specifies the change speed of the
inverter active power.
-
6
Derated by fixed
active power (kW)
Adjusts the active power output of
the inverter by fixed value.
-
7
Derated by active
power % (%)
Adjusts the active power output of
the inverter by percentage.
If this parameter is set to
100
, the inverter outputs
based on the maximum
output power.
8
Night-time reactive
power output
In some specific application
scenarios, a power grid company
requires that the inverter can
perform reactive power
compensation at night to ensure
that the power factor of the local
power grid meets requirements.
-
9
Enable reactive
power parameters
at night
When this parameter is set to
Enable
, the inverter outputs
reactive power based on the
setting of
Reactive power
compensation at night
.
Otherwise, the inverter executes
the remote scheduling command.
This parameter is displayed
when
Night-time reactive
power output
is set to
Enable
.
10
Night-time reactive
power
compensation
(kVar)
During the reactive power
compensation at night, the
reactive power is scheduled by
fixed value.
This parameter is displayed
when
Night-time reactive
power output
and
Enable
reactive power parameters
at night
are set to
Enable
.
11
Reactive power
change gradient
(%/s)
Specifies the change speed of the
inverter reactive power.
-
12
Plant active power
gradient (min/
100%)
Specifies the rate of active power
rise due to sunlight changes.
-
13
Average active
power filtering time
(ms)
Specifies the period of active
power rise due to sunlight
changes. This parameter is used
with
Plant active power gradient
.
-
14
Power factor
Specifies the power factor of the
inverter.
-
15
Reactive power
compensation (Q/S)
Specifies the reactive power output
by the inverter.
-
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
74