Figure 7-13
Power adjustment parameters (special user)
----End
Parameters
No.
Parameter
Description
Remarks
1
Remote power
schedule
If this parameter is set to
Enable
,
the inverter responds to the
scheduling instruction from the
remote port. If this parameter is
set to
Disable
, the inverter does
not respond to the scheduling
instruction from the remote port.
-
2
Schedule instruction
valid duration (s)
Specifies the time for maintaining
the scheduling instruction.
When this parameter is set
to 0, the scheduling
instruction takes effect
permanently.
3
Maximum active
power (kW)
Specifies the output upper
threshold for the maximum active
power to adapt to different market
requirements.
-
4
OFF at 0% power
limit
If this parameter is set to
Enable
,
the inverter shuts down after
receiving the 0% power limit
command. If this parameter is set
to
Disable
, the inverter does not
shut down after receiving the 0%
power limit command.
-
SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1
User Manual
7 Man-Machine Interactions
Issue 05 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
73