No.
Parameter
Description
Remarks
14
VRT exit
hysteresis
threshold
Specifies the LVRT/HVRT recovery threshold.
● This parameter is
displayed when
LVRT
or
HVRT
is
set to
Enable
.
● LVRT recovery
threshold =
Threshold for
triggering LVRT +
VRT exit hysteresis
threshold
● HVRT recovery
threshold =
Threshold for
triggering HVRT +
VRT exit hysteresis
threshold
15
Grid voltage
jump
triggering
threshold (%)
Specifies the LVRT or HVRT threshold for
triggering a transient voltage jump of a power
grid. A transient voltage jump indicates that the
inverter cannot immediately disconnect from
the power grid when the power grid is
abnormal due to transient changes.
-
16
Zero current
due to power
grid fault
Certain countries and regions have
requirements on the output current during
high/low voltage ride-through. In this case, set
this parameter to
Enable
. After this parameter
is set to
Enable
, the output current is less than
10% of the rated current during high/low
voltage ride-through.
This parameter is
displayed when
LVRT
or
HVRT
is set to
Enable
.
17
Active
islanding
protection
Specifies whether to enable the active islanding
protection function.
-
18
Automatic
OFF due to
communicati
on
interrupted
The standards of certain countries and regions
require that the inverter must shut down after
the communication is interrupted for a certain
time.
-
19
Automatic
ON due to
communicati
on resumed
If this parameter is set to
Enable
, the inverter
automatically starts after communication
recovers. If this parameter is set to
Disable
, the
inverter needs to be started manually after
communication recovers.
-