6 Battery Test
Issue 07 (2019-12-30)
Copyright © Huawei Technologies Co., Ltd.
64
6
Battery Test
6.1 Internal Resistance Test
Prerequisites
Batteries are in float charging state,
Single string current
of battery value is 0 A, and no
battery overtemperature alarm, battery overvoltage alarm, or battery thermal runaway alarm
has been generated.
Context
To identify a faulty battery, you are advised to test the battery internal resistance.
If conditions are met, the iBAT will automatically perform an internal resistance test periodically.
Procedure
Step 1
Log in to the UPS WebUI.
Step 2
On the
Monitoring > Control > iBOX Control
page, specify
iBOX No.
and click
Measure
.
Step 3
On the
Monitoring > Real-time Data > Battery String
page, select
Battery String_N
to
view the detailed information about each battery string.
Criteria for determining that the iBAT detection function is normal:
The voltage displayed on the WebUI is in the range of the measured voltage ± 0.2%.
The temperature displayed on the WebUI is in the range of the measured temperature ±
1°C.
The internal resistance value is displayed for each battery.
----End