5 System Commissioning
Issue 07 (2019-12-30)
Copyright © Huawei Technologies Co., Ltd.
48
The UPS software version UPS5000 V100R003C01SPC408 is used for reference.
On the WebUI and LCD of some UPSs, iBOX is named CIM, and iBAT is named BIM.
Procedure
Step 1
Set UPS parameters.
UPS LCD
a.
On the UPS LCD home screen, choose
System Info > Settings > Battery Settings
,
and set
Number of battery strings
.
b.
On the UPS LCD home screen, choose
System Info > Settings > iBOX Settings
,
and set
Basic Param.
,
Advanced Param.
, and
Batt. String Config
.
Figure 5-5
iBOX Settings
Figure 5-6
Basic Param.