iBattery 3.0
User Manual
3 Installing Devices
Issue 07 (2019-12-30)
Copyright © Huawei Technologies Co., Ltd.
25
Figure 3-10
Installing Hall effect sensors (battery string without a neutral wire)
Step 3
Connect the cable between the iBOX and the Hall effect sensors.
If the battery string is configured with a neutral wire, the currents of the positive and
negative battery string cables need to be detected. If the battery string is not configured
with a neutral wire, only the current of the positive or negative battery string cable needs
to be detected.
If an iBOX manages multiple battery strings, first connect the Hall effect sensors on
battery string 1 respectively to the corresponding ports on the iBOX. Then connect the
Hall effect sensors on battery string 2 to the iBOX in the same way, and so on.
Battery string with a neutral wire
Figure 3-11
Cable connections to Hall effect sensors (1)
Cable Label
iBOX Port
B_HALL1
HALL_1