The temperature exceeds the threshold.
Step 1
Check that the server where the drive resides provides proper cooling. If the server reports no
temperature alarm and the fan modules are operating properly, go to
Step 2
Check that the equipment room where the drive resides provides proper cooling. If the
equipment room temperature is normal, go to
Step 3
Obtain drive logs by following instructions in
5.7.3 One-Click Log Collection
and contact
Huawei technical support.
----End
l
An internal error downgrades the NVM subsystem reliability.
l
The medium is read-only.
l
Device backup fails.
Step 1
Obtain drive logs by following instructions in
5.7.3 One-Click Log Collection
and contact
Huawei technical support.
----End
5.11 Indicator Status Description
5.11.1 ES3000 SSD Disk Indicator State Descriptions
The indicators on the front panel of the drive bay display the working status of the ES3000
V5, as shown in
. The amber/blue indicator is the fault indicator, and the green
indicator is the working status indicator.
describes the indicators when the SSD is
installed in a Huawei server.
Figure 5-6
ES3500P V5/ES3600P V5 front view
Table 5-2
ES3000 SSD indicator state description
Activity Indicator
(Green)
Fault Indicator
(Amber/Blue)
State Description
Off
Off
The NVMe SSD disk cannot be
detected.
On
Off
The NVMe SSD disk is detected and
working properly.
2 Hz
Off
Data access to the NVMe SSD disk is
in progress.
ES3000 V5 NVMe PCIe SSD
User Guide
5 Maintenance and Upgrade
Issue 07 (2019-03-19)
Copyright © Huawei Technologies Co., Ltd.