Bare crimping terminals need to be crimped on both ends of the power cable. Choose different
terminals according to different devices.
shows the OT bare crimping terminal, and
shows the single-line cord end terminal.
Figure 6-7
OT bare crimping terminal
Figure 6-8
Single-line cord end terminal
6.2.3 E8000E-X16 AC-input Power Cable
If the E8000E-X16 uses AC power sources, power cables include:
l
Cables between the AC-DC convertors and the E8000E-X16.
l
Cables between the AC-DC convertors and the AC power distribution cabinet.
Cables Between the AC-DC convertors and the E8000E-X16:
Place the AC-DC convertors as near to the device as possible. If the distance between the AC-
DC convertors and the device is longer than 3 m, the cabling scheme is shown in
. If the distance is shorter than and equal to 3 m, the cabling scheme
Table 6-9
Cable types and cable terminals of the AC-input power cable
Item
Description
Cable Type
Monitor and
alarm cable
Monitor and Alarm Cable,3m,D9M,CC4P0.48B(S),D9M
NEG power
cable (-48 V)
Wire,450/750V,60227 IEC 02(RV)16mm
2
,blue,85A
RTN power
cable
Wire,450/750V,60227 IEC 02(RV)16mm
2
,black,85A