79
80
LP-532 REV. 8.13.2014
LP-532 REV. 8.13.2014
Main components Replacement Instructions
3. Flame Detection Sensor
4. Gas Leak Detector
1. Close the gas shut off valve
2. Turn the power off
3. Disconnect all the electrical connection to the
main controller
5. Pluck away PCB’s gas leakage detector.
6. Replace leak detection with new component.
7. Assembly is in the reverse order as the part was
repaired.
8. Open the gas shut off valve
9. Turn the power on
10. Turn the unit on and ensure proper operation.
1. Close the gas shut off valve
2. Turn the power off
3. Disconnect all the electrical connection to the
flame detection sensor
4. Rotate flame detection sensor 45 degrees
clockwise and pull forward.
5. Replace flame detection sensor with new
component.
6. Assembly is in the reverse order as the part was
repaired.
7. Open the gas shut off valve
8. Turn the power on
9. Turn the unit on and ensure proper operation.
NOTE:
Ensure the flame detection sensor is
properly secured.
Chapter 5 Replacement instructions
Main components Replacement Instructions
5. Air pressure swtich (APS)
1. Close the gas shut off valve
2. Turn the power off
3. Disconnect the electrical connection to the APS
4. Separate hose from Air Pressure switch.
5. Loosen Air Pressure switch bracket’s two
screws.
6. Replace APS with new component
7. Assembly is in the reverse order as the part was
repaired.
8. Open the gas shut off valve
9. Turn the power on
10. Turn the unit on and ensure proper operation.
Chapter 5 Replacement instructions
WARNING
Failure to turn the power off to the appliance
before repair could result in serious injury or