background image

HP Modular Cooling System G2 
Installation Overview 

 

 

Summary of Contents for MCS G2

Page 1: ...HP Modular Cooling System G2 Installation Overview ...

Page 2: ...osed external valves If valves are installed on the external pipe work that could potentially trap fluid inside the MCS unit special precautions must be taken In order to prevent severe plumbing failure due to extreme pressure use an expansion tank with a preinstalled safety valve in the plumbing circuit connected to the unit MCS G2 kit contents HP MCS G2 unit installed on an HP 10000 G2 Series Ra...

Page 3: ...r plate steps 4 through 6 if you are routing your hoses through the hole in the raised floor 5 Loosen the jam nut and then raise the unit by lowering the two rear leveling feet on both the MCS unit and the rack until you can remove the rear caster plate 6 Remove the rear caster plate 7 Lower the unit by raising the two rear leveling feet on both the MCS unit and the rack so that the MCS unit can m...

Page 4: ...onnections b Open the ball valves at the main hose connections 14 Plug the network cable into the RJ 45 connector on the power inlet box 15 Plug the other end of the network cable to your network connection IMPORTANT Do not connect the power cords into a power supply 16 Plug the primary power cord into the power connector on the left WARNING To reduce the risk of electric shock or damage to the eq...

Page 5: ...er cord where it can be walked on or pinched by items placed against it Pay particular attention to the plug electrical outlet and the point where the cord extends from the storage system 1 Plug the power cords into an appropriate power source 2 Connect the network cable to your network infrastructure NOTE If you have a DHCP server you can change the IP address through the web interface instead of...

Page 6: ...serial number enter 3 Serial Number MCS d To return to the Main Menu screen press Esc 8 Access the HP Modular Cooling System Configuration Utility a From the Main Menu screen enter 1 Network Configuration The Menu Network Configuration screen appears b Enter 1 IP Configuration The IP Configuration screen appears c To disable DHCP enter 4 Enable Disable DHCP d Enter 1 IP Address and then enter the ...

Page 7: ...rs 11 Log in through the web interface a Enter the user name in the User Name field The default user name is Admin b Enter the password in the Password field The default password is Admin c Click Sign In 12 Verify that the water source is available and turned on by viewing the Water Flow status in the Overview menu 13 Click Setup Accounts and then change the default Web Admin and Web User password...

Page 8: ...ess of the management module The login screen appears 3 Log in through the web interface a Enter the user name in the User Name field The default user name is Admin b Enter the password in the Password field The default password is Admin c Click Sign In 4 Click Setup Network a Select the radio button to disable DHCP enabled is the default setting b Click Save Settings c Change the IP address in th...

Page 9: ...rmation on adjusting the management module settings through the web interface see the HP Modular Cooling System G2 Web Interface User Guide located on the Documentation CD included with this product Automatic Door Release Kit To view the HP Automatic Door Release hardware installation instructions see the documentation that shipped with that kit To enable the automatic door release functionality 1...

Page 10: ...and services are set forth in the express warranty statements accompanying such products and services Nothing herein should be construed as constituting an additional warranty HP shall not be liable for technical or editorial errors or omissions contained herein Microsoft and Windows are U S registered trademarks of Microsoft Corporation Part Number 463068 001 December 2007 ...

Reviews: