Install a lightning arrester at the input end of the power supply to enhance the
lightning protection capability of the power supply.
Install a special lightning arrester at the input end of outdoor signal lines (for
example, E1 line) to which interface modules of the router are connected to enhance
the lightning protection capability.
For the installation of a power lightning arrester and a signal lightning arrester, refer to
“Installing a Power Lightning Arrester (Lightning Protection Busbar) (Optional)” and “Selecting
and Installing a Signal Lightning Arrester (Optional)” in Chapter 4 “Installing the Router”.
Cabinet-Mounting Requirements
When installing the router in a cabinet,
Install the router in an open cabinet if possible. If you install the router in a closed
cabinet, make sure that the cabinet is equipped with a good ventilation system.
Install the router on a shelf in view of the heavy weight of the router.
Make sure that the cabinet is sturdy enough to support the weight of the router and
installation accessories.
Make sure that the size of the cabinet is appropriate for the router, and that there is
enough clearance around the left and right panels of the router for heat dissipation.
For the sake of heat dissipation and device maintenance, it is recommended that
the front and rear of the cabinet should be at least 0.8 m (31.5 in.) away from walls
or other devices, and that the headroom in the equipment room should be no less
than 3 m (118.1 in.).
Safety Precautions
Installation and removal of the unit and its accessories must be carried out by qualified
personnel. You must read all of the Safety Instructions supplied with your device before
installation and operation.