VISIONPRO® 8000 SMART THERMOSTAT
33-00096—04
68
NOTE:
This feature requires a wired sensor for outdoor
temperature limits, or Internet connection for
temperature and humidity lockouts.
Options are:
• Ventilation Low Temperature Lockout Setpoint
(Off, -20° to 40° F)
• Ventilation High Temperature Lockout Setpoint
(Off, 80° to 110° F)
• Ventilation High Dewpoint Lockout Setpoint
(Off, 65° to 85° F)
Refer to the information below if you need assistance
setting the High Dewpoint Lockout.
• Higher than 80: Extremely uncomfortable
• 75 to 80: Very uncomfortable
• 70 to 74: Quite uncomfortable
• 65 to 69: Somewhat uncomfortable
Ventilate on High Indoor Humidity (ISU
1016)
If set to ventilate on high indoor humidity, the ventilator
turns on to remove excess humidity if the indoor humidity
is 10% above the Humidification setting. The thermostat
must be in the heat mode to ventilate on high indoor
humidity.
Set up Ventilation
Some screens shown in this section may not appear on the
thermostat, depending on how you set up ventilation.
1.
Select the Ventilation Type in ISU 1000. See Fig. 157.
Fig. 157.
2.
Select the terminals wired to the Ventilator (or Fresh
Air Damper). See Fig. 158.
Fig. 158.
3.
Select the Ventilation Control Method. See “Ventila-
tion Control Methods (ISU 1005)” on page 67 for
more information. See Fig. 159.
Fig. 159.
4.
Select the Ventilation Fan Control. See “Ventilation
Fan Control (ISU 1006)” on page 67 for more infor-
mation. See Fig. 160.
NOTE:
ISU 1006 is only displayed if the Ventilation
Type is ERV / HRV. The thermostat controls
the fan if the Ventilation Type is Fresh Air
Damper.
Fig. 160.
5.
If ASHRAE was selected for ISU 1005, select the
Number of Bedrooms and Size of House. See
Fig. 161.
Fig. 161.
6.
If ASHRAE was selected for ISU 1005, enter the
Equipment Ventilation Rate (CFM). Be sure this set-
ting corresponds with the actual ventilation speed.