VISIONPRO® 8000 SMART THERMOSTAT
25
33-00096—04
407
Min. Cool Recovery
Ramp Rate
Off
1° F/hr to 20° F/hr
3° F/hr
Commercial
Off: The cooling system will begin recovery at the
time that is scheduled.
When a Minimum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Minimum Recovery Ramp Rate based on the
rate that the cooling system can recover at for a hot
day in your region. Default setting is 3° F / hour.
Set an Outdoor Temperature that is representative of
a hot day in your region to be associated with the
Minimum Recovery Ramp Rate. The thermostat will
begin recovery at the optimal time based on a
calculated ramp rate, allowing the system to recover
on time and save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
407
Min. Cool Recovery
Outdoor Temp
Off
-20° F to 100° F
90° F
Commercial
Off: The cooling system will begin recovery at the
time that is scheduled.
When a Minimum Recovery Ramp Rate is set, the
thermostat will begin recovery early to ensure the
temperature is reached at the scheduled time.
Set a Minimum Recovery Ramp Rate based on the
rate that the cooling system can recover at for a hot
day in your region. Default setting is 3° F / hour.
Set an Outdoor Temperature that is representative of
a hot day in your region to be associated with the
Minimum Recovery Ramp Rate. The thermostat will
begin recovery at the optimal time based on a
calculated ramp rate, allowing the system to recover
on time and save energy during changing outdoor
conditions.
During recovery, the setpoint changes at a rate in
degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Notes