VISIONPRO® 8000 SMART THERMOSTAT
33-00096—04
22
400
Scheduled Periods
2 or 4 periods per day
4 periods per day
Both
Residential:
4 Periods = Wake, Leave, Return, Sleep
2 Periods = Wake, Sleep
Commercial:
4 Periods = Occupied 1, Unoccupied 1, Occupied 2,
Unoccupied 2
2 Periods = Occupied 1, Unoccupied 1
401
Pre-Occupancy
Purge
Off
1 hour
2 hour
3 hour
Off
Commercial
Runs the fan 1 to 3 hours before each occupied
period to provide a comfortable workplace upon
arrival.
402
Type of Override
Standard
Initiate Occupancy
Standard
Commercial
Standard:
The system maintains temperatures
programmed for the occupied and unoccupied
time periods. Pressing OVERRIDE will allow the
user to make a temporary schedule change.
Initiate Occupancy:
The system maintains temperature at an energy
saving level until the user touches the message
center area on the thermostat. Note: The
message center displays
Press HERE to Start
Occupancy
. The system will then maintain a
comfortable temperature until the occupied
period ends. This option is recommended for
cost savings when the workplace is used
infrequently or arrival times change from day to
day (example - schools). After the user touches
Press HERE to Start Occupancy
, the user will
still be able to perform a standard
OVERRIDE
of
the schedule.
403
Override Duration
No Limit
1 to 12 Hours
3 hours
Commercial
When the user presses the OVERRIDE button, the
thermostat will maintain the new temperature for at
least 1 hour. The user can adjust the Hold Until time
from 1 hour to the amount set for the Override
Duration (1-12 hours). Default setting is 3 hours. If
set to No Limit, the user can adjust the Hold Until
time up to 24 hours.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Notes