ControlNet Fiber Media
Specifications
R210
Experion PKS ControlNet Fiber Optic Implemenation Guide
27
10/04
Honeywell
ControlNet Cable
Drop cable from ControlNet tap
See Experion PKS Specifications. The Experion PKS
specifications can be found on the Honeywell website:
. Just follow the
Experion PKS product links.
Weight
Approximately 230g (0.5lb)
Short-Distance Fiber Module TC-RPFS01
Parameter
Description
General
Backplane Power
Requirements
300mA at 5Vdc maximum
Fiber Operating Wavelength
650nm (red)
Optical Power Budget
4.2dB
Communication Rate
5M bits/s
Operating Conditions
Ambient Temperature
0 C to 60 C (32 F to 140 F)
Storage Temperature
–40 C to 85 C (–40 F to 185 F)
Maximum Relative Humidity
5 to 95%, non-condensing
Shock Test
Operating: 30g peak acceleration, 11 (+/-1) ms pulse
width
Non-Operating: 50g peak acceleration, 11 (+/-1) ms
pulse width
Vibration Test
5g @ 10 to 500Hz, according to IEC 68-2-6
Physical
Fiber Optic Cable Type
200/230 micron HCS (Hard-Clad Silica)
Fiber Optic Termination Type
Versalink V-System
Weight
Approximately 140g (0.3lb)