ControlNet Fiber Media
Installing ControlNet Repeater Adapter
R210
Experion PKS ControlNet Fiber Optic Implemenation Guide
11
10/04
Honeywell
Step
Action
1
Be sure the DIN rail is connected to protective earth ground.
2
Remove the protective cover from the BNC connector and connect a
ControlNet T or Y Tap with a drop cable to it.
(
Note
that when a Repeater Adapter and Fiber Module pair (Hub) are used in
series to
only
repeat a fiber link to another fiber link (see Figure 6), there is
no need to connect a coax drop cable or terminator to the BNC connector. In
this case, it may be desirable to cover the left, red, (COAX) LED (which will
be lit to indicate no cable is connected). Otherwise, use a coax drop cable to
make a connection to a local trunk cable as noted above.)