ControlNet Fiber Media
Installing ControlNet Fiber Module
R210
Experion PKS ControlNet Fiber Optic Implemenation Guide
15
10/04
Honeywell
Step
Action
1
Remove the protective cover from the backplane bus connector on the
Repeater Adapter or other Fiber Module already connected to a Repeater
Adapter. Remove the protective cover from the bus connector on the left side
of the Fiber Module to be installed.
2
Orient the Fiber Module so the top of the unit is over the top of the DIN rail to
the right of the installed Repeater Adapter or Fiber Module.
3
Slightly rotate the Terminal Base to slip its top mounting flange on the top of
the DIN rail.
4
•
Press the Fiber Module down flush with the DIN rail so its locking tab
snaps into place, securing the module to the rail. If necessary, you can use
a screwdriver to manually retract the lock while pressing the module firmly
against the rail and then releasing it when in position.
•
Carefully slide the module to the left until its bus connector is fully seated
in the mating Repeater Adapter or Fiber Module bus connector.
(Note that you can connect up to four Fiber Modules to one Repeater
Adapter. Be sure you secure the modules together with DIN rail anchors to
minimize the chance of lost communications or damage to the modules. )
5
Leave the protective cover on the backplane bus connector on the right side
of the module until you are ready to make the connection.