The meter reader list is divided into four sections and can only be displayed in the following order:
MAG LIST
SECTIONS
DESCRIPTION
1
Alarm Codes
(Displayed only if any alarms are active)
2
Mag List 1
(Item codes 130-135)
3
Live Parameter Display (Item code 129)
4
Mag List 2
(Item codes 075 - 086)
Except for the Alarm Codes, each subsection listed above is configurable. Refer to the descriptions below and
the flowchart in figure 15 on page 50 for configuration details and the sequence of events that occur during a non-
default meter reader list.
Mag List 1
Mag List 1 consists of six item codes (130-135) which define what items will appear in section 2 of the meter
reader list. Normally, Display Test, Uncorrected Volume and Corrected Volumes are the item assigned to Mag
List 1. However, any instrument item code can be placed into Mag List 1. If less than six items are required,
place the value “255” into the item code location after the last desired Mag List 1 item. When the Mag List 1
item values are displayed, all eight digits on the LCD are used, unless the volume items are configured for fewer
digits using Item Codes 096 and 097.
Example #1:
Suppose Display Test, Corrected Volume, Uncorrected Volume, Gas Pressure and Gas Temperature are the
only items desired for Mag List 1. Since only five items are listed, the Mag List 1 configuration would appear
as follows:
Item Item Legend
Selected Item
Description
Code#
Item
130
Mag List 1 Item 1 #
061
Display Test
131
Mag List 1 Item 2 #
000
Corrected Volume
132
Mag List 1 Item 3 #
002
Uncorrected Volume
133
Mag List 1 Item 4 #
008
Gas Pressure (not Live)
134
Mag List 1 Item 5 #
026
Gas Temperature (not Live)
135
Mag List 1 Item 6 #
255
(End-Of-List)
Live Parameters Display
The Live Parameter Display will allow up to three parameters to appear in section 3 of the meter reader list. The
only three parameters that may be a live display are: Live PCor Gas Pressure, Live Gas Temperature and Live
PLog Gas Pressure. These should not be confused with item codes 008 (PCor Gas Pressure), 026 (Gas
Temperature) and 420 (PLog Gas Pressure). If item codes 008, 026 and 420 are part of the meter reader list,
the values displayed are PCor gas pressure, gas temperature, and PLog gas pressure placed into memory at the
time of the initial mag wand input, not live readings. When item codes 008, 026 or 420 are encountered during
a Meter Reader Mode, the values previously placed in memory are recalled and then displayed.
The purpose of providing a Live Gas Pressure and Live Gas Temperature is twofold. First, it will allow the meter
Summary of Contents for Mini-AT
Page 2: ...2 www honeywell com ...
Page 138: ...138 www honeywell com Mini AT User Guide Mini AT Door ...
Page 140: ...140 www honeywell com Mini AT User Guide Meter Mount Mini AT ...
Page 142: ...142 www honeywell com Mini AT User Guide Wall Mount Mini AT ...
Page 144: ...144 www honeywell com Page 144 Mini AT User Guide ...
Page 145: ...145 Page 145 Mini AT User Guide ...
Page 146: ...146 www honeywell com Page 146 Mini AT User Guide ...
Page 147: ...147 Page 147 Mini AT User Guide ...
Page 148: ...148 www honeywell com Page 148 Mini AT User Guide ...
Page 149: ...149 Page 149 Mini AT User Guide ...
Page 150: ...150 www honeywell com Page 150 Mini AT User Guide ...