Item
No.
Item Name
Description
————————————————————————————————————————
165
RBX ALARM ENABLE
Code (
0-1
) to determine the type of instrument alarm operation.
When the RBX function (Report By Exception) is disabled, all
instrument alarms operate as in previous versions of firmware, i.e.,
alarms stay active until manually cleared. When RBX is enabled,
instrument alarms are automatically cleared after the alarm
parameter returns to its normal operating range, buffered by a user-
specified dead band. Exceptions; A/D Fault andSwitch Faults
1 & 2. “Alarm”, “Alarm Ack” and “Alarm Clear” entries are time-
stamped into the Alarm Logger to provide details of alarm activity.
Also see Items 237 & 174 for related functions.
Select:
0
- Standard Alarms------
Default
1
- RBX Alarms
166
PCOR PRESS DEAD BAND A hysteresis band that provides a buffer below the PCor Pressure
Hi limit (item 010) and above the PCor Pressure Lo limit (item
011) when alarms are automatically cleared by RBX operation.
The user-specified value determines the magnitude of the band.
The PCor pressure measurement (item 008) must pass completely
through the dead band before the pressure alarm is automatically
cleared.
Default
= 5.00 PSIG
167
TMP DEAD BAND
A hysteresis band that provides a buffer below the Gas
Temperature Hi limit (item 028) and above the Gas Temperature
Lo limit (item 027) when temperature alarms are automatically
cleared by RBX operation. The user-specified value determines
the magnitude of the band. The temperature measurement (item
026) must pass completely through the dead band before the
temperature alarm is automatically cleared.
Default
= 10.00 F
168
BATT DEAD BAND
A hysteresis band that provides a buffer above the Battery Low
Limit Voltage (item 049) when the main Battery Low alarm is
automatically cleared by RBX operation. The user-specified value
determines the magnitude of the band. The battery voltage
measurement (item 048) must pass completely through the dead
band before the battery low alarm is automatically cleared.
Default
= 1.00 Volt
Summary of Contents for Mini-AT
Page 2: ...2 www honeywell com ...
Page 138: ...138 www honeywell com Mini AT User Guide Mini AT Door ...
Page 140: ...140 www honeywell com Mini AT User Guide Meter Mount Mini AT ...
Page 142: ...142 www honeywell com Mini AT User Guide Wall Mount Mini AT ...
Page 144: ...144 www honeywell com Page 144 Mini AT User Guide ...
Page 145: ...145 Page 145 Mini AT User Guide ...
Page 146: ...146 www honeywell com Page 146 Mini AT User Guide ...
Page 147: ...147 Page 147 Mini AT User Guide ...
Page 148: ...148 www honeywell com Page 148 Mini AT User Guide ...
Page 149: ...149 Page 149 Mini AT User Guide ...
Page 150: ...150 www honeywell com Page 150 Mini AT User Guide ...