Item
No.
Item Name
Description
————————————————————————————————————————
451
PLOG PRESSURE HIGH
This item indicates if a PLog high pressure alarm was
generated. During a PLog sample (Item 401), if the
measurement for item 420 (PLog GAS PRESSURE) is greater
than the value entered at item 455 (PLog PRESS HILIM), an
alarm is initiated and is indicated by placing dots on the LCD
and ‘11111111’ at item 451. ‘00000000’ at item 451 indicates
there is no PLog pressure high alarm. The alarm indicators
will remain active until manually cleared (by software) or
automatically when RBX is enabled. The PLog Pressure High
Limit value (item 455) is user selectable and is normally set
somewhere between 50 and 100% of transducer range.
Default
= 00000000
452
PLOG PRESSURE LOW
This item indicates if a PLog low pressure alarm was
generated. During a PLog sample (Item 401), if the
measurement for item 420 (PLog GAS PRESSURE) is a value
less than the value entered at item 456 (PLogPRESS LOLIM),
an alarm is initiated and is indicated by placing dots on the
LCD and ‘11111111’ at item 452. ‘00000000’ at item 452
indicates there is no PLog pressure low alarm. The alarm
indicators will remain active until manually cleared (by
software) or automatically when RBX is enabled. The PLog
Pressure Low Limit value (item 456) is user selectable and is
normally set somewhere between 0 and 50% of transducer
range.
Default
= 00000000
455
PLOG PRESS HILIM
High limit for PLog pressure, initiates alarm (item 451), if
exceeded by item 420.
Default
= 099999.99
456
PLOG PRESS LOLIM
Low limit for PLog pressure, initiates alarm (item 452), if
higher than item 420.
Default
= 0.00
459
PLOG PRESS DEADBAND A hysteresis band that provides a buffer below the PLog
Pressure Hi limit (item 455) and above the PLog Pressure Lo
limit (item 456) when alarms are automatically cleared by
RBX operation. The user-specified value determines the
magnitude of the band. The PLog pressure measurement (item
420) must pass completely through the dead band before the
pressure alarm is automatically cleared.
Default
= 5.00 PSIG
Summary of Contents for Mini-AT
Page 2: ...2 www honeywell com ...
Page 138: ...138 www honeywell com Mini AT User Guide Mini AT Door ...
Page 140: ...140 www honeywell com Mini AT User Guide Meter Mount Mini AT ...
Page 142: ...142 www honeywell com Mini AT User Guide Wall Mount Mini AT ...
Page 144: ...144 www honeywell com Page 144 Mini AT User Guide ...
Page 145: ...145 Page 145 Mini AT User Guide ...
Page 146: ...146 www honeywell com Page 146 Mini AT User Guide ...
Page 147: ...147 Page 147 Mini AT User Guide ...
Page 148: ...148 www honeywell com Page 148 Mini AT User Guide ...
Page 149: ...149 Page 149 Mini AT User Guide ...
Page 150: ...150 www honeywell com Page 150 Mini AT User Guide ...