107
Page 107
Mini-AT User Guide
Item
No.
Item Name
Description
————————————————————————————————————————
126
BAUD RATE CODE
Code (
0 - 7
) to select the instrument’s baud rate for a local serial
connection. A communication error will result if the baud rate
does not match the baud rate of the connected computer. The
38.4 Kbaud selection is provided to achieve the fastest possible
download times. A separate item (Item code 272) provides setting
the baud rate for a modem connected at terminal strip TB2.
Select:
0
- 9600------
Default
4
- 600
1
- 4800
5
- 300
2
- 2400
6-
19200
3
- 1200
7-
38400
128
MAG ALARM
Code (
0 or 1
) to enable or disable the clearing of all active alarms
ACKNOWLEDGE
using the mag wand. During the Meter Reader List, an
“E.E.E.E.E.E.E.E” display will appear after scrolling through all
active alarms. Allowing the instrument to time-out (1-minute) at
this display will clear all alarms. If instead, the mag wand is used
to scroll to the next mag list item before the “E.E.E.E.E.E.E.E”
display times-out, the alarms are not cleared. This feature is most
useful if alarms need to be cleared and a laptop computer is not
available. If item 128 is configured for “Disabled”, the
“E.E.E.E.E.E.E.E” pattern will never be displayed.
Select:
0
- Disabled
1
- Enabled
Default
129
LIVE DISP ENABLE
Code (
0 - 3
) to select the display of live gas pressure and/or live
temperature as part of the Meter Reader List. If enabled, the live
parameter(s) will appear after the display of the last Mag List 1, but
before any Mag List 2 items. Both live gas pressure and
temperature have a 30 minute time-out instead of the usual 1
minute.
Default = 3 - Live PCor & T
Select:
0
- None
4
- Live PLog
1
- Live PCor
5
- Live PCor & PLog
2
- Live T
6
- Live T & PLog
3
- Live PCor & T
7
- Live PCor, T & PLog
130
MAG LIST 1 ITEM 1
Item number of the first item displayed in the Meter Reader List,
unless there are active alarms. Active alarms are always displayed
prior to the selected mag list items. Any Mini-AT item may be
entered as a mag list item. Enter a 255 for this item if the Mag List
1 function is to be disabled. See the section on using the Meter
Reader List for more information.
Default
= 061 (Display Test)
Summary of Contents for Mini-AT
Page 2: ...2 www honeywell com ...
Page 138: ...138 www honeywell com Mini AT User Guide Mini AT Door ...
Page 140: ...140 www honeywell com Mini AT User Guide Meter Mount Mini AT ...
Page 142: ...142 www honeywell com Mini AT User Guide Wall Mount Mini AT ...
Page 144: ...144 www honeywell com Page 144 Mini AT User Guide ...
Page 145: ...145 Page 145 Mini AT User Guide ...
Page 146: ...146 www honeywell com Page 146 Mini AT User Guide ...
Page 147: ...147 Page 147 Mini AT User Guide ...
Page 148: ...148 www honeywell com Page 148 Mini AT User Guide ...
Page 149: ...149 Page 149 Mini AT User Guide ...
Page 150: ...150 www honeywell com Page 150 Mini AT User Guide ...