Mini-AT User Guide
Item
No.
Item Name
Description
————————————————————————————————————————
111
FIXED TEMP FACT
Code (
0 - 2
) that selects Live or Fixed Factor Temperature. When
enabled for Fixed Factor (code 1), the Temperature Factor entered
at Item 045 will be used for temperature correction, instead of a
live calculation based on the input from the temperature probe.
NOTE: if item 111 is “Fixed”, a value
must
be entered at Item 045.
It may also be necessary to enter a value at Item 026 (Gas
Temperature) if Supercompressibility is “Live”. If the selection for
Item 111 is code 2 (Super), the total correction factor will include
the Fixed Factor entered at Item 045 (usually 1.0000), while using
the Live gas temperature from the temperature probe for the
supercompressibility calculation. The code 2 selection was made
available for sites with TC meters
Select:
0
- No Fixed Factor (Live)
Default
1
- Fixed Factor
2
- Fixed Factor Temperature with Live
Measured Temperature for
Supercompressibility Computations.
112
PCOR XDUCER TYPE
Code (
0 or 1
) to indicate the type of pressure transducer
installed. Since the equations to calculate pressure correction
and supercompressibility are dependant upon the transducer
type, make sure the selection at items 087 and 112 are properly
configured for the installed transducer.
Select:
0
- Gauge------
Default
1
- Absolute
113
HI RES COR VOL
Display of the fractional portion (to the 4th decimal) of item 000
(Totalized Corrected Volume) with the last three CorVol integers
for reference. Example: if the value at item 000 equals ‘12345678
MCF’, item 113 may appear as ‘678.2477 MCF’. The four
decimal places are useful during field calibration checks when
using a small number of meter revolutions.
Default
= 000
.
0000
114
METER SCALING
Scaling factor for uncorrected volume input applied to the value
selected at item 098 (Meter Index Rate). Usually used if the
volume input is a value other than 0.1, 1, 5, 10, 100, 1000, as is
the case when an HFI board or 4-pole magnet disc is installed.
Default
= 1.0000
Summary of Contents for Mini-AT
Page 2: ...2 www honeywell com ...
Page 138: ...138 www honeywell com Mini AT User Guide Mini AT Door ...
Page 140: ...140 www honeywell com Mini AT User Guide Meter Mount Mini AT ...
Page 142: ...142 www honeywell com Mini AT User Guide Wall Mount Mini AT ...
Page 144: ...144 www honeywell com Page 144 Mini AT User Guide ...
Page 145: ...145 Page 145 Mini AT User Guide ...
Page 146: ...146 www honeywell com Page 146 Mini AT User Guide ...
Page 147: ...147 Page 147 Mini AT User Guide ...
Page 148: ...148 www honeywell com Page 148 Mini AT User Guide ...
Page 149: ...149 Page 149 Mini AT User Guide ...
Page 150: ...150 www honeywell com Page 150 Mini AT User Guide ...