Honeywell
23
Between touches with same polarity
1000VAC 1minute
Between touches with different polarity
1000VAC 1minute
Insulation
Between touch and winding
1000VAC 1minute
Surge voltage
Between touches with same polarity
1500V (10×160us)
Length of open time
3ms max
Length of closed time
3ms max
Mechanical
50×106 times (3Hz)
Longevity
Electrical
200×103 times (0.5Hz)
Temperature
-40 ~
℃
+70
℃
RS232
RS232 port is reserved for technical support diagnosis and upgrade.
RS485
When the DVR receives a camera control command, it transmits that
command up the coaxial cable to the PTZ device. RS485 is a single-
direction protocol; the PTZ device cannot return any data to the unit. To
enable the operation, connect the PTZ device to the RS485 (A,B) input on
the DVR. See
Figure 3-3
.
Since RS485 is disabled by default for each camera, you must enable the
PTZ settings first. This series DVRs support multiple protocols such as
Pelco-D, Pelco-P.
To connect PTZ devices to the DVR:
1. Connect RS485 A,B on the DVR rear panel.
a. Ensure the decoder has the same grounding with the DVR,
otherwise you will not be able to control the PTZ. Shielded twisted wire
is recommended, and the shielded layer should be used to connect the
ground.
b. Avoid high voltage. Ensure proper wiring and some thunder
protection measures.
Summary of Contents for HSVR-04
Page 2: ......
Page 47: ...Honeywell 39 Figure 4 14 Motion Detection Zone Setting Figure 4 15 PTZ Activation Setting ...
Page 100: ...Understanding of Menu Operations and Controls 92 Figure 5 38 The Shutdown Menu ...
Page 103: ...Honeywell 95 Figure 6 2 The Internet Options Window ...
Page 133: ...Honeywell 125 Figure 6 39 The Detection Setup Menu Figure 6 40 The Detection Zone Setup ...