Parameters [51]
Galaxy Flex Installer Manual
96
1=No of Alarms
The total number of zone activations signalled in any one set period.
The selectable values are 0 to 10 where 0 is unlimited.
2=Unset Limit
The number of activations logged from any one zone in any one unset
period. The selectable values are 0 to 10 where 0 is unlimited. The
default is 3. Fire alarms are not restricted by this parameter.
3=Set Limit
The number of activations logged from any one zone in any one set
period. The selectable values are 0 to 10 where 0 is unlimited. The
default is 3. Fire alarms are not restricted by this parameter.
Note:
This feature only affects Contact ID, SIA and Microtech communication formats.
Confirm Time [51.49]
Use this option to set the maximum time between two separate zones for a confirmed alarm
to be generated up to a maximum of 99 minutes, which is equivalent to the complete set
period, with a default of 30 minutes.
Trigger Mod [51.50]
Ensure a trigger module has been wired onto the system before you enable this option.
Similarly, disable this option before you disconnect a trigger module from the system. When
this option is enabled, outputs 1001 and 1002 on the panel are converted to operate as
control lines for the trigger module and cannot be used as outputs directly. Outputs 1001 and
1002 are transferred to the trigger module.
Use
Program Outputs [53]
to programme the function of trigger outputs 0001 to 0008.
Keypad Access [51.54]
Use this option to select how the keypad unsets the system. There are two options:
1=Always
Keypad always unset the system.
2=Except Entry
Except when entry time is running. This ensures that users are
unsetting using a fob or MAX tag (portable device).
Confirm Operation [51.55.1]
Use this option to control when confirmed intruder alarms can be triggered. The choices are:
1=Before Entry
Confirmed alarms can be triggered before starting entry time
only.
2=Except entry
Confirmed alarms can be triggered any time except during the
entry delay period. (PD6662: 2004)
3=Always
Confirmed alarms are always enabled. (PD6662: 2010)
Confirm Entry Timeout [51.55.2]
Use this option to control whether exit type zones can cause confirmed alarms after an entry
timeout.