Section 3: Programming the IGSMHS
3-7
PROMPTS
ENTRY
OPTIONS
DESCRIPTION
27
Flt Rel ON Y/N
(N)_
[Y], [N]
If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module fault. For conditions that trip
the fault relay refer to
Module Supervision Features
in
Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring for
Module Fault Relay
in Section 2.
UL:
Must be set to "Y."
28
Pwr Loss Rpt Y/N
(Y)_
[Y], [N]
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A restore
report is sent within 1-3 hours after power is restored.
UL Standard Installations
(using transformer and
battery)
:
Must be set to "Y".
29
Low Bat Rpt Y/N
(Y)_
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low battery restore is
automatically sent when the low battery condition
clears.
UL
Standard Installations
(using transformer and
battery)
:
Must be set to "Y".
30
Tamper Rpt Y/N
(Y)_
[Y], [N]
Sends a tamper report when the module detects a
tamper condition. A tamper restore is automatically
sent when the tamper condition clears.
UL:
Must be set to "Y."
Important Information Regarding Zone Input Options
ECP mode
supports two optional hardwire zone input triggers by making connections to the module’s zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
(V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
(V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
(EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
UL Installations
, V+ is to be set as inverted and V– as non-inverted.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting (NOT for UL installa-
tions), which allows time for the user to abort false alarms.
NOTE:
Optional hardwire zones report in ADEMCO High-Speed format.
31
Enable Zn6 Y/N
(N)_
[Y], [N]
Enables alarm reporting for zone 6.
If [N], skip to Prompt 36: "Enable Zn7."
32
Zn6 Trigger Type
(V+)_
(V+)
(V–)
(EOLR)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
UL:
V+ must be set as inverted and V– as
non-inverted.
33
Invert Zn6 Y/N
(N)_
[Y], [N]
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
34
Restore Zn6 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 6.
35
Delay Zn6 (secs)
(00)_
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 6.
UL:
Must be set to 00.
36
Enable Zn7 Y/N
(N)_
[Y], [N]
Enables alarm reporting for zone 7.
If [N], skip to Prompt 41: "Use DHCP."
Summary of Contents for AlarmNet IGSMHS
Page 2: ......
Page 10: ...IGSMHS Installation and Setup Guide 1 6 ...
Page 18: ......
Page 40: ...IGSMHS Installation and Setup Guide 3 22 ...
Page 44: ...IGSMHS Installation and Setup Guide 4 4 ...
Page 52: ...IGSMHS Installation and Setup Guide A 2 ...
Page 54: ...IGSMHS Installation and Setup Guide B 2 ...
Page 58: ...IGSMHS Installation and Setup Guide D 2 ...
Page 59: ...NOTES ...
Page 60: ...NOTES ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...