3-1
S E C T I O N 3
Programming the IGSMHS
General Information
The IGSMHS is designed to deliver alarms via the Internet to an AlarmNet central station or
via the AlarmNet-G network, using GSM (Global System for Mobile) technology when the
Internet is not available.
The IGSMHS uses 256 bit AES (Rijndael) encryption which is required for certain
government installations.
The IGSMHS module requires an AlarmNet–I account. For new installations, please obtain
the account information from the central station prior to programming this module. For
replacement installations, the AlarmNet-i account is created automatically when the module is
registered.
You can program a IGSMHS by one of the following methods:
Through the AlarmNet Direct website
Through use of a 7720P Programming Tool
Through a programming mode in the control panel, on panels that support this option
UL
Only ECP and Zone Trigger modes have been evaluated by UL.
Programming the Control Panel to work with the IGSMHS
For Residential and Commercial control panels, there are certain programming field settings
that must be adhered to for using the IGSMHS. (For programming information, please refer
to the appropriate control panel guides.) Ensure the following programming fields are set:
RESIDENTIAL / COMMERCIAL Control Panels (Such as the VISTA-10P, 15P, and 20P series.)
UL:
These control panels have not been evaluated by UL.
Programming Field
Setting
29 Menu Mode for IP/GSM Enable
1 (Enable LRR.)
54 Dynamic Signaling Delay
0 (Dialer and LRR reports go out at the same time.)
55 Dynamic Signaling Priority
0 (Primary dialer reports first.)
COMMERCIAL Control Panels (Such as the VISTA-128
/
250 series.)
Programming Field
Setting
32 Primary Subscriber's Acct No.
nnnn (Required for the communicator to report.)
56 Dynamic Signaling Delay
00 (Dialer and LRR reports go out at the same time.)
57 Dynamic Signaling Priority
1 (Communicator, as first reporting.)
58 Comm Central Station #1
Category Enable
111111 (All events will be reported to the primary Central
Station.)
59 Comm Central Station #2
Category Enable
000000 (If Central Station #2 is not used.)
111111 (If Central Station #2 is used.)
#
93 Menu Mode
Zone programming – set Zone 803 for Type 05.
Device programming – set Address 03 for Type 06 (LRR).
Summary of Contents for AlarmNet IGSMHS
Page 2: ......
Page 10: ...IGSMHS Installation and Setup Guide 1 6 ...
Page 18: ......
Page 40: ...IGSMHS Installation and Setup Guide 3 22 ...
Page 44: ...IGSMHS Installation and Setup Guide 4 4 ...
Page 52: ...IGSMHS Installation and Setup Guide A 2 ...
Page 54: ...IGSMHS Installation and Setup Guide B 2 ...
Page 58: ...IGSMHS Installation and Setup Guide D 2 ...
Page 59: ...NOTES ...
Page 60: ...NOTES ...
Page 61: ...NOTES ...
Page 62: ...NOTES ...