HV100 Series High Performance Current Vector Inverter
61
When the inverter is powered on, the panel frequency increment is initialized to the value saved in EEPROM during the
last power failure.
1:not store
When the inverter is powered on, the panel frequency increment is initialized to 0.
LED 10-digit: stop keep
0: keep
When the inverter stops, the frequency set value is the final modified value.
1: Stop not keep
When the inverter stops, the set frequency is restored to 00.09.
LED 100-digit:
key
、
Negative frequency adjustment
0: invalid
1: valid
When the selection is valid, the positive and negative adjustment of frequency can be realized by operating keyboard
keys.
00.08
Digital setting 2
0000
~
1111
0000
LED single digit: power down store
0:store
When the inverter is powered on, the terminal frequency increment is initialized to the value saved in EEPROM during
the last power failure.
1:not store
When the inverter is powered on, the terminal frequency increment is initialized to 0.
LED 10-digit: stop keep
0: keep
When the inverter stops, the frequency set value is the final modified value.
1: Stop not keep When the inverter is not stopped, the set frequency is restored to 00.10.
LED 100-digit: UP/DOWN negative frequency regulation
0: invalid
1: valid
Select valid, terminal UP/DOWN can realize the positive and negative adjustment of frequency.
00.09
Frequency source digital given 1 setting
0.00Hz
~【
00.13
】
upper limit frequency
50.00
When the frequency channel is defined as digital given 1 (the main frequency source is 0 and the auxiliary frequency
source is 0), this function parameter is the initial set frequency given by the digital frequency of the inverter panel.
00.10
Frequency source digital given 2 setting
0.00Hz
~【
00.13
】
upper limit frequency
50.00
When the frequency channel is defined as digital given 2 (the main frequency source and auxiliary frequency source are
1), this function parameter is the initial set frequency of the frequency given by the inverter terminal.
00.11
Setting of auxiliary frequency source weight coefficient K
0.01
~
10.00
1.00
K is the weight coefficient of auxiliary frequency source
00.12
Max output frequency
Low frequency band: max {50.00, [00.13]} ~ 300.00; high frequency band: max
{50.0, [00.13]} ~ 300.0
50.00
00.13
Upper limit frequency
【
00.14
】~【
00.12
】
50.00
00.14
Lower limit frequency
0.00Hz
~【
00.13
】
0.00