HV100 Series High Performance Current Vector Inverter
113
If the ratio of the maximum value to the minimum value in the three-phase output current is greater than this coefficient,
and the duration exceeds 10 seconds, the inverter will report the output current imbalance fault E-13. When 10.08 = 1.00,
the output current unbalance detection is invalid.
10.19
Reservation
Reservation
0
10.20
Treatment of PID feedback disconnection
0
~
3
0
0: no action
1: Alarm and keep running at the frequency of disconnection time
2
:
Protective action and free parking
3: Alarm and slow down to zero speed according to the set mode
10.21
Feedback disconnection detection value
0.0
~
100.0%
0.0%
The maximum value given by PID is taken as the upper limit value of feedback disconnection detection value. In the
feedback disconnection detection time, when the feedback value of PID is continuously less than the feedback
disconnection detection value, the inverter will make corresponding protection actions according to the setting of 10.20.
10.22
Feedback disconnection detection time
0.0
~
3600.0S
10.0
Feedback the duration after disconnection and before protection action.
Figure 010-4 Closed-loop feedback loss detection timing diagram
10.23
Setting of FDT1 current detection level
0.0
~
200.0%
0.0
See function No.62 in 07.18 ~ 07.21 for details.
10.24
Selection of RS485 communication abnormal action
0
~
2
1
0: protection action and free stop
1: Alarm and maintain the status quo to continue running
2: Alarm and shut down according to the set shutdown mode
10.25
RS485 communication timeout detection time
0.0
~
100.0s
5.0
If RS485 communication fails to receive the correct data signal within the time interval defined by this function code, it
is considered that RS485 communication is abnormal, and the inverter will make corresponding actions according to the
setting of 10.24. When this value is set to 0.0, RS485 communication timeout detection is not performed.
10.26
Keypad communication abnormal action selection
0
~
2
1
Time
Closed-loop
feedback
value
Detection
value
Loss
detection
Loss does
not detect
Loss
detection