HV100 Series High Performance Current Vector Inverter
100
0: deceleration and shutdown
1
:
free stop
08.14
Deviation between feedback and set pressure when entering sleep
0.0
~
10.0%
0.5%
This function parameter is only valid for the second sleep mode.
08.15
Sleep threshold
0.00
~
200.0%
100.0%
This threshold is the percentage of the given pressure, and this function parameter is only valid for the first sleep mode
relative to the setting.
08.16
Awakening threshold
0.00
~
200.0%
90.0%
08.15 defines the feedback limit when the inverter enters the sleep state from the working state. If the actual feedback
value is greater than the set value, and the frequency output by the inverter reaches the lower limit frequency, the inverter
will go to sleep after the delay waiting time defined in 08.17 (i.e. running at zero speed).
08.16 defines the feedback limit of inverter from sleeping state to working state. When PID polarity selects positive
characteristic, if the actual feedback value is less than the set value (or when PID polarity selects negative characteristic, if
the actual feedback value is greater than the set value), the inverter will get out of sleep and start working after the delay
waiting time defined in 08.18.
Figure F8-5 Schematic diagram of the first sleep mode
Figure F8-6 Schematic diagram of the second sleep mode
Sleep min value
PID settings
Wake up min value
Output frequency
Lower rate frequency
Zero frequency
PID feedback
Sleep detection
time
Sleep
Wake-up
Wake-up
detection time
PID set value
Wake up min value
Output frequency
Lower rate frequency
Zero frequency
Sleep
Sleep
Wake-
up
PID
feedback
PID sleep delay PID wake-up delay
PID sleep delay
Setting
Deviation